The CIC-152-N can monitor and control dosing and/or injection systems. This unit will control 2 separate systems.

 

Features:

  • Large, bright tri-color L.E.D. display
  • Two adjustable set points keep TDS levels within a range
  • Minimum and maximum control points will activate relay controls via switching dry contacts
  • Can control two different devices (ex. a pump and a valve)
  • Two alarms (maximum and minimum levels) can be set independently of the control points
  • Digital calibration
  • On-screen temperature display
  • On-screen range & control indicator lights (green, yellow or red)
  • Includes one sensor probe
  • Available with the NaCl conversion factor 

Dual Dosing/Injection TDS/EC Controller

SKU: CIC-152
C$527.85Price
  • TDS Range: 0 - 5000 ppm
  • EC Range: 0 – 9999 µS
  • Temperature Range: 1 - 80 °C; 33 - 176 °F
  • Resolution: 0.1 ppm (0-999); 1 ppm (1000-9999)
  • Accuracy: +/- 2%
  • Conversion Factor: NaCl (avg. 0.5)
  • Calibration: Digital calibration by push button
  • Factory Calibration: 1413 µS
  • Set Points: Adjustable by push button
  • Relay Control: The unit will transmit an analog signal (simple switch) via open or closed contacts to a device (e.g. pump/valve) when the ppm/µS level reaches the maximum TDS/EC limit (Control Point 2) or the minimum TDS/EC limit (Control Point 1)
  • The contacts are switched back to the normal position once the TDS returns to the acceptable range
  • Relay Voltage: 5V (attached devices must have their own power supply)
  • Alarm: Two independent alarms (set by user)
  • Display: Bright 5/8″ L.E.D. display
  • Probe: 1/2″ bushing (NPT), 3 meter (9.8 ft) shielded cable (model SP-1-PSC)
  • Power source: AC 110V / AC 220V

28 Vaughan Road

Welland, ON, L3B 5Y1

Mon-Thurs 9-5, Fri 9-4:30

Closed Sat & Sun

© 2019 Water Concepts

info@waterconcepts.ca

P: 905-788-1784

F: 905-788-3456

*Phone is regularly monitored after-hours